Switchboard WiresBare Copper WiresBuilding WiresInstrumentation Cables600V Multi-Conductor Control Tray Cables600V Multi-Condutor Power Cables and VFD Cables600V Interlocked Armored Instrumentation Cables600V Interlocked Armor Control Cables600V-35kV Interlocked Armor Power CablesFlexible Portable CordsFlexing Portable Mining CablesMV-105 Power CablesIN STOCK Belden and Belden Equals or Similar         
 
 
 
                                     
All Categories > 600V-35kV Interlocked Armor Power Cables > Type MC-IAC Interlocked Armor Power Cables 600 Volts > View Items  

Type MC-IAC Interlocked Armor Power Cables 600 Volts

Check up to five results to perform an action.

APPLICATIONS:
Where NEC jurisdiction applies; as Type MC cable, 90 deg.C. in wet or dry locations; for installation aerially, in conduit, cable trays, in underground ducts, with messenger or direct buried, for power and control circuits not exceeding 600 volts in manufacturing and processing plants, substations and generating stations. When installed per the NEC, cables meet requirements of OSHA. Permitted for use in Class I, Class II, Division 2, Class III Division 1 and 2 hazardous locations per the NEC. Suitable for direct burial.
 
CONSTRUCTION:
Three-, or four conductors of stranded copper, XLP (Cross-Linked Polyethylene) insulated, phase-identified, conductors cabled with a stranded copper ground wire in one interstice, cable tape, aluminum or galvanized steel interlocked armor, black PVC (Polyvinyl Chloride) jacket overall, surface printed.
 
STANDARDS:
*   Conductors conform to ASTM B-3 & B-8.
*   Insulation conforms to UL Standard 44, and is approved as Type XHHW-2.
*   MC Type Cable per UL 1569.
*   Cables designed to pass the IEEE-383 ribbon burner flame test.
*   Cable suitable for Sunlight Resistant, Direct Buried and “For CT Use” applications.
*   Cables meet requirements of ICEA S-95-658.

To download the datasheet please click here



Search Items



    border="0" Printable Page  
    Email Email This Page  
    Save To Favorites Save To Favorites
  

 DOWNLOADS 

Type MC-IAC Power Cable 600V SPEC. SHEET
(PDF, 72KB)

Compare Items
   
  Results 1 - 32 of 32 1 

Part #

Conductor Size

No. of Conductors

O.D. Over PVC JKT. (in)

Alum Weight (lbs/mft)

Galv. Steel Weight (lbs/mft)

Conductor Color Coding Methods

9-651-G 8 AWG 3 .850 410 lbs/m 500 lbs/m N/A
9-652-G 6 AWG 3 .950 550 lbs/m 660 lbs/m N/A
9-653-G 4 AWG 3 1.02 735 lbs/m 855 lbs/m N/A
9-654-G 2 AWG 3 1.16 1080 lbs/m 1215 lbs/m N/A
9-655-G 1 AWG 3 1.34 1310 lbs/m 1470 lbs/m N/A
9-656-G 1/0 AWG 3 1.38 1575 lbs/m 1805 lbs/m N/A
9-657-G 2/0 AWG 3 1.64 1885 lbs/m 2130 lbs/m N/A
9-658-G 3/0 AWG 3 1.68 2315 lbs/m 2620 lbs/m N/A
9-659-G 4/0 AWG 3 1.94 2820 lbs/m 3110 lbs/m N/A
9-660-G 250 MCM 3 2.02 3360 lbs/m 3740 lbs/m N/A
9-661-G 300 MCM 3 2.09 3900 lbs/m 4370 lbs/m N/A
9-662-G 350 MCM 3 2.35 4490 lbs/m 4900 lbs/m N/A
9-662-G4 400 MCM 3 2.36 5060 lbs/m 5670 lbs/m N/A
9-663-G 500 MCM 3 2.59 6215 lbs/m 6700 lbs/m N/A
9-664-G 600 MCM 3 2.79 7350 lbs/m 7860 lbs/m N/A
9-665-G 750 MCM 3 2.97 9065 lbs/m 9655 lbs/m N/A
9-670-G 8 AWG 4 .910 500 lbs/m 590 lbs/m N/A
9-671-G 6 AWG 4 1.02 685 lbs/m 800 lbs/m N/A
9-672-G 4 AWG 4 1.11 955 lbs/m 1130 lbs/m N/A
9-673-G 2 AWG 4 1.34 1360 lbs/m 1565 lbs/m N/A
9-674-G 1 AWG 4 1.56 1680 lbs/m 1930 lbs/m N/A
9-675-G 1/0 AWG 4 1.64 2000 lbs/m 2280 lbs/m N/A
9-676-G 2/0 AWG 4 1.68 2420 lbs/m 2735 lbs/m N/A
9-677-G 3/0 AWG 4 1.94 2995 lbs/m 3315 lbs/m N/A
9-678-G 4/0 AWG 4 2.02 3605 lbs/m 4010 lbs/m N/A
9-679-G 250 MCM 4 2.27 4320 lbs/m 4735 lbs/m N/A
9-680-G 300 MCM 4 2.36 5200 lbs/m 5650 lbs/m N/A
9-681-G 350 MCM 4 2.49 5950 lbs/m 6400 lbs/m N/A
9-682-G 400 MCM 4 2.59 6570 lbs/m 7180 lbs/m N/A
9-683-G 500 MCM 4 2.79 8045 lbs/m 8590 lbs/m N/A
9-684-G 600 MCM 4 2.97 9520 lbs/m 10115 lbs/m N/A
9-685-G 750 MCM 4 3.27 11825 lbs/m 12490 lbs/m N/A