Switchboard WiresBare Copper WiresBuilding WiresInstrumentation Cables600V Multi-Conductor Control Tray Cables600V Multi-Condutor Power Cables and VFD Cables600V Interlocked Armored Instrumentation Cables600V Interlocked Armor Control Cables600V-35kV Interlocked Armor Power CablesFlexible Portable CordsFlexing Portable Mining CablesMV-105 Power CablesIN STOCK Belden and Belden Equals or Similar         
 
 
 
                                     
All Categories > Flexible Portable Cords > Type SOOW Flexible Cords > View Items  

Type SOOW Flexible Cords

Check up to five results to perform an action.

APPLICATION:
Type SOOW flexible cords are permitted for use per Article 400 of the NEC in wiring for industrial machinery, motors and associated equipment, portable tools and equipment, and temporary electrical power and lighting installations for construction sites. Also suitable for indoor and outdoor use, for use in dry locations not to exceed min. -40 deg.C. or max. 90 deg.C., wet locations and other applicable locations; or when exposed to oil or coolant at temperatures not to exceed 60 deg.C. Ideal for flex applications in harsh environments where the highest degree of oil resistance and extended service life are essential.
 
CONSTRUCTION:
Flexible stranded copper conductors, heat, moisture and oil resistant EPR (Ethylene-Propylene-Rubber) insulated, color-coded* conductors cabled with fillers and a separator wrapped around the assembly to promote easier jacket removal, heat, moisture and oil resistant flexible CPE (Chlorinated Polyethylene) jacket overall, surface printed.
 
STANDARDS:
*   Copper conductors per ASTM B-3 & B-174.
*   Cables conform to UL-62, Flexible Cord and Fixture Wire.
*   Cables conform to requirements of Federal and Military Specification JC-580B.
 

 






    border="0" Printable Page  
    Email Email This Page  
    Save To Favorites Save To Favorites
  

 DOWNLOADS 

Conductor Color Coding Methods
(PDF, 319KB)

Type-Soow SPEC. SHEET
(PDF, 64KB)

Compare Items
   
  Results 1 - 16 of 16 1 

Part #

Conductor Size

No. of Conductors

O. D. (in)

Conductors Insulation (mils)

Jacket Insulation (mils)

Weight (lbs/mft)

11-1524 16 AWG 3 0.39 30 60 95
11-1526 14 AWG 3 0.54 45 80 170
11-1528 12 AWG 3 0.60 45 95 225
11-1530 10 AWG 3 0.66 45 95 290
11-1532 8 AWG 3 0.84 60 110 477
11-1534 6 AWG 3 0.98 60 125 670
11-1536 4 AWG 3 1.14 60 140 956
11-1538 2 AWG 3 1.31 60 155 1310
11-1544 16 AWG 4 0.42 30 60 115
11-1546 14 AWG 4 0.58 45 80 205
11-1548 12 AWG 4 0.65 45 95 270
11-1550 10 AWG 4 0.72 45 95 355
11-1552 8 AWG 4 0.93 60 125 616
11-1554 6 AWG 4 1.06 60 140 837
11-1556 4 AWG 4 1.26 60 155 1225
11-1558 2 AWG 4 1.46 60 170 1712